The Server Environment Monitoring System monitors critical environmental conditions, such as temperature, humidity, liquid presence, motion, intrusion, and vibration. When a sensor goes out of range of a configurable threshold, the system will notify you via email, LEDs, alarm beacon, web page, network management (SNMP), and SMS messages (via external GSM modem).
Also known as: Remote Environment Monitoring System, monitor computer rooms, server room monitoring alert, IP temperature sensor, humidity sensor, computer room temperature
Monitors Threats:
  • Temperature
  • Humidity
  • Water Leakage
  • Power
  • Intrusion
  • Smoke
Now Supporting
  • SNMPv3
  • Logging of data
  • USB Option (flash drives or
    3G modem)
  • User-programmable IP camera snapshots
  • Designed and Manufactured in the U.S.A.
  • ROHS Compliant Enterprise Server Environment Monitoring System
  • CE Compliant Enterprise Server Environment Monitoring System
Scroll Down to Request a Quote
The ENVIROMUX® Server Environment Monitoring System monitors critical environmental conditions, such as temperature, humidity, liquid water presence, power, intrusion, and smoke. When a sensor goes out of range of a configurable threshold, the system will notify you via email, LEDs, alarm beacon, siren, web page, network management (SNMP), voice phone calls (via Automatic Voice Dialer System), and SMS messages (via external GSM or 3G modem). The system includes three internal sensors: temperature, humidity and power. It also supports 16 external configurable sensors and eight digital input sensors.
  • Monitor and manage server room environmental and security conditions over IP.
  • Create alarm signals with customized input parameters.
  • Four output relays for control of external devices.
    • Relays activate upon alarm or via the user interface.
  • Supports IP network video cameras for live view of any facility.
    • One integrated view - see different Web cameras side-by-side with physical and environmental parameters.
  • Monitor (ping) up to 64 IP network devices.
    • Alerts are sent if devices are not responding.
  • Available sensors include: temperature, humidity, smoke, water, glass break, motion, vibration, 4-20 mA converter, voltage detector, and more.
  • Stores up to 1,000 event and data entries in system data log.
    • The log can be downloaded as a tab-delimited plain text file, viewed via the web interface, or sent to up to 16 remote IP addresses using syslog.
    • Automatically log to USB flash drive w/ USB model.
  • Integrates with various Open Source monitoring packages — Nagios and MRTG.
  • Provides power supply for all sensors.
  • Internal battery backup.
    • Alerts are sent when there is a power outage and when power returns.
  • Available with optional dual power for connection to two separate power sources.
  • Available with optional 48VDC or 24VDC power.
  • Up to six units can be used together to increase the number of sensors connected.
    • Connect up to six units via Ethernet connection or up to four units using CAT5 expansion cables to increase the number of sensors connected.
    • Uses a single Web interface for all systems connected.
  • Available with optional USB port for connecting USB modem or for downloading log data to USB flash drive.
  • Optional intuitive graphical software provides an easy-to-use, unified interface for both monitoring and configuring up to 3,000 ENVIROMUX-SEMS-16 units and all connected sensors.
  • 1RU rack mount case is standard.
  • Meets the electrostatic discharge (ESD) immunity requirements of IEC/EN 61000-4-2.
  • Use in data centers, co-lo sites, web hosting facilities, telecom switching sites, POP sites, server closets, or any unmanned area that needs to be monitored.
Server Environment Monitoring System Specifications Drawing
1. Power Port
  • 110 or 230 VAC at 50 or 60 Hz via IEC connector. (Country-specific power supply cable included.)
  • Power consumption: 100 W max.
  • Connection for Earth Ground.
  • Fuse protection.
  • Optional 48VDC power (not shown).
    • Accepts 36~72VDC (48VDC nominal).
  • Optional 24VDC power (not shown).
    • Accepts 20~32VDC (24VDC nominal).
  • Optional dual power (not shown).
    • Available on AC, 48VDC, and 24VDC models.
    • If the first power source fails, the unit will automatically, without interruption, switch over to the second power source before switching to the battery backup.
2. RJ45 Sensor Ports
  • Sixteen RJ45 modular jacks for connecting NTI temperature, humidity, temperature/humidity, liquid detection, smoke detection, glass break, vibration and motion sensors.
3. Digital Inputs
  • Eight screw terminals pairs for connecting dry contact devices.
  • Input voltage: 0VDC to +25VDC.
  • Provides +12VDC, 50 mA.
  • Fuse protection.
4. Output Relays
  • Four screw terminal pairs.
  • Potential-free relay switch contacts.
  • Maximum switching load: 0.5A at 100 VAC, 1A at 30VDC
5. Beacon Port
  • One screw terminal pair.
  • Provides +12VDC, 180 mA to supply an alarm beacon.
  • Fuse protection
6. Siren Port
  • One screw terminal pair.
  • Provides +12VDC, 180 mA to supply a siren.
  • Fuse protection
7. Expansion Ports
  • Two RJ45 jacks.
  • A maximum of 4 systems can be cascaded to increase the number of sensor ports.
  • Uses a single Web interface for all systems connected.
8. Console Port
  • One female DB9 RS232 serial port for terminal access.
9. AUX Port
  • One male DB9 RS232 serial port for controlling and monitoring external equipment, such as a GSM or 3G modem.
    • GSM modems supported: Teltonika WirelessCom/G10, Enfora GSM1218, MultiTech MTCBA-G-F2, Wavecom Fastrack M1306
  • 3G modems supported: NetComm N3GS003, Option iCON 452
10. AUX Power Port
  • Provides +12 VDC, 150 mA.
  • Fuse protection
11. Ethernet Port
  • One 10/100 Base-T Ethernet port with RJ45 Ethernet connector.
Protocols
  • HTTP, SNMP V1/V2c/V3, SMTP, TCP/IP, Syslog, SNTP, Telnet, DHCP, SSL
  • Operates and configures via HTTP/HTTPS web page, Telnet or RS232 interface.
  • Alerts are sent using email, syslog, SMS messages and/or SNMP traps when any monitored environmental condition goes out of range of a configurable threshold.
    • Alerts are posted in message log, which is accessible through Web user interface. The log can be downloaded as a tab-delimited plain text file.
    • Sends notifications of alerts to a maximum of 17 email addresses, SNMP addresses and/or cell phone numbers. The users can configure the schedule when they will be alerted, as well as customize the e-mail subject line for each sensor alert.
    • SNMP traps have unique OID's (Object Identifiers) for each sensor.
    • OIDs for sensor and contact values for ENVIROMUX-SEMS-16.
Internal Temperature Sensor
  • Applications from 32 to 104°F (0 to 40°C).
  • Accurate to within ±1.35°F (±0.75°C).
Internal Humidity Sensor
  • Applications from 20 to 80% relative humidity at temperatures between 32 to 104°F (0 to 40°C).
  • Accurate to within ±5% relative humidity.
Internal Power Sensor
  • Measures mains voltage: 0 to 255 VAC.
  • Measures battery voltage: 0 to 20 VDC.
  • Alerts are sent when there is a power outage and when power returns.
Back-up Battery
Optional USB Port
  • Female USB Type A connector for connecting USB modem or for downloading log data to USB flash drive.
Dimensions
  • WxDxH: 19x9.5x1.75 in (483x241x44 mm)
Environmental
  • Operating temperature: 32 to 100°F (0 to 38°C).
  • Storage temperature: -22 to 140°F (-30 to 60°C).
  • Operating and Storage Relative Humidity: 17 to 90% non-condensing RH.
MTBF
  • ENVIROMUX-SEMS-16: 56,709 hrs.
Regulatory Approvals
  • CE, RoHS
Warranty
  • Two years
Web Interface (view product demo)
  • Full configuration via Web-page.
  • Support for Extended ASCII characters.
  • Configure sensor thresholds and timing, alarm methods, alert formats and system data log.
  • View current sensor values and alert status.
    • All sensors connected to the ENVIROMUX-SEMS-16 can be viewed on one summary page.
    • "Simulate"/"Clear" buttons for each sensor to test alert settings.
  • View entries stored in the system data log.
    • The log can be downloaded as a tab-delimited plain text file.
  • Configure IP information (address, subnet mask, default gateway, DNS, etc.) and user administrative settings.
  • Administrate up to 16 users plus a root administrator.
  • Permissions, schedule and alert methods are configurable for each user.
  • Up to 8 users can access the web page at one time.
RS232 Control
  • Display and configure network settings (IP address, subnet mask, default gateway, DNS, SMTP, etc.), Enterprise settings, and time settings.
  • View current values and alert statuses for sensors/digital inputs/IP devices.
  • Configure SNMP
  • Serial baud rate: 9,600 to 115,200bps.
  • Data format: 1 start bit, 8 data bits, no parity, 1 stop bit.
Telnet
  • Display and configure network settings (IP address, subnet mask, default gateway, DNS, SMTP, etc.), Enterprise settings, and time settings.
  • View current values and alert statuses for sensors/digital inputs/IP devices.
  • Configure SNMP
  • Security is ensured by password.
Network Operation
  • SNMP support, allowing integration into network management platforms.
  • Updating the system firmware.
Front Panel LED Indicators
  • "INT ALERT" — internal sensor goes out of range of a configurable threshold.
  • "EXT ALERT" — external sensor goes out of range of a configurable threshold.
  • "LOW BAT" — backup battery is low.
  • "CHECK LOG" — message is posted to the log.
  • "PWR" — indicates device is powered.
Open Source Monitoring Integration
Optional Management Software

Application Drawings

  • Enterprise Server Environment Monitoring System
    Enterprise Server Environment Monitoring System
    Configuration and cable illustration of a system monitoring room conditions including temperature, humidity, liquid and vibration.

Application Notes

  • Alert Notifications Sent via Email, LEDs, Web Page, Network Management (SNMP), and SMS Messages
    Loading image...
    The ENVIROMUX™ Server Environment Monitoring System gives total security to IT centers by providing early warnings about potential problems via email, LEDs, web page, network management (SNMP), and SMS messages (via external GSM modem).
  • Send Email Alerts from a Private Network to a Public Mail Relay Server
    Loading image...

    The ENVIROMUX-SEMS-16 present on a private 10.x.x.x network is capable of sending email alerts to a public 153.x.x.x mail relay server.

    Note: To use a DSL type router in this set up, set a gateway in the network settings of the ENVIROMUX-SEMS-16 to allow traffic to be sent to the 153.x.x.x network. The IP address of the router on the private 10.x.x.x network is the gateway.

  • Monitor Telect™ GMT Fuse Panels with Relay Outputs.
    Loading image...
    The ENVIROMUX™ Server Environment Monitoring System monitors Telect™ GMT fuse panel relay outputs and sends alerts in case of power loss, fuse break, or bay alarms. Configure digital inputs as "normally open" for proper operation.
  • Accessing Sensor Data using HTTP Requests
    Loading image...

    Sensor data can be retrieved from the ENVIROMUX® Server Environment Monitoring System using the HTTP requests shown in the table below. The value for "s" is the value of the sensor. For example, to access the current value for External Sensor number 1 you can use:

    http://[ip address of the ENVIROMUX-SEMS-16 to access]/ext_sens_val.html?s=1

    Type
    External Sensor ext_sens_val.html?s=0 ext_sens_stat.html?s=0
    Internal Sensor int_sens_val.html?s=0 int_sens_stat.html?s=0
    Power Sensor pow_sens_val.html?s=0 pow_sens_stat.html?s=0
    Digital Input dig_inp_val.html?s=0 dig_inp_stat.html?s=0
    Output Relays rly_out_val.html?s=0 NA

CAD Drawings

  • ENVIROMUX-SEMS-16
    Loading image...
  • "We have been using the NTI ENVIROMUX-SEMS-16 sensor system for a few weeks now. So far we have been more than pleased with the scalability, ease of configuration, and functionality of the unit. We recommend this product to data centers of every size."

    Nick Gray
    Cyber Wurx LLC
    St Louis, MO, USA
  • "I'd like take this opportunity to thank you for the outstanding level of service I have received from you. Our ENVIROMUX-SEMS-16 has been installed and is the fit that we were looking for to monitor potential environmental threats. The interface is very user friendly. We will be purchasing additional sensors as the need arises and would highly recommend your product."

    Josh Bell
    Shields Health Care
    Velancia, CA, USA
  • "We have been using the NTI ENVIROMUX-SEMS-16 sensor system for a few weeks now. So far we have been more than pleased with the scalability, ease of configuration, and functionality of the unit. We recommend this product to data centers of every size."

    William Bakhenberg
    DBS International
    Bethlehem, PA, USA
  • "NTI's ENVIROMUX-MINI has allowed our federal agency to monitor temperature in critical areas should the building's HVAC fail. I was so impressed by it that we upgraded our main server room from the ENVIROMUX-MINI to the ENVIROMUX-SEMS-16, which will allow us to send cellular messages during power failures that affect our demarc. As the Network Engineer responsible for monitoring the agency's network faults and environmental variables, I can fulfill my duties knowing that NTI's products will alert me of a potential failure long before anyone becomes affected by it."

    Philip Hutinet
    Washington, DC, USA
  • "While shopping for environment monitoring equipment for our remote facilities, I came across NTI's website. One call got me all the information I needed on the ENVIROMUX-SEMS-16. After sharing the information with everyone, we couldn't believe the flexibility of these units. NTI allowed us to demo one of the units for 30 days. The quality and flexibility of the product is great, plus NTI has a sensor for most anything you want to monitor. We placed another call to order two more units and all the sensors we needed. Now we can completely monitor and protect our remote sites just by logging in through a web browser."

    Patrick Beard
    Rice Belt Telephone Co
    Weiner, AR, USA
  • "Between myself and my assistant, we are responsible for approximately 360 network devices at 4 different facilities. Several of these 360+ devices are wireless access points, routers, switches and our biggest nemeses, network based IP time clocks which are used for time and attendance purposes as well as logging on and off of jobs to track time.

    "Being able to ping for up status of the non PC network IP devices through the ENVIROMUX-SEMS-16 allows my assistant and I to attack a down device before it becomes a crisis."

    Michael Wagner
    Metal Technologies, Inc.
    West Allis, WI, USA
  • "I am very satisfied with the performance of the ENVIROMUX-SEMS-16, and I especially like the ease of operation."

    James Husband
    Reserach Data Inc
    Richmond, VA, USA

(0)Enterprise Server Environment Monitoring System

NTI Part # Power Qty
ENVIROMUX-SEMS-16 AC
ENVIROMUX-SEMS-16DP Dual AC
ENVIROMUX-SEMS-16-24V 24V DC
ENVIROMUX-SEMS-16-24VDP Dual 24V DC
ENVIROMUX-SEMS-16-48V 48V DC
ENVIROMUX-SEMS-16-48VDP Dual 48V DC

Collapse all Expand all Related Items :

(0)Server Environment Monitoring System Management Software

NTI Part # Description Qty
ENVIROMUX-MS-SEMS0010 Manage 10 ENVIROMUX-SEMS-16
ENVIROMUX-MS-SEMS0050 Manage 50 ENVIROMUX-SEMS-16
ENVIROMUX-MS-SEMS0100 Manage 100 ENVIROMUX-SEMS-16
ENVIROMUX-MS-SEMS0500 Manage 500 ENVIROMUX-SEMS-16
ENVIROMUX-MS-SEMS3000 Manage 3000 ENVIROMUX-SEMS-16

(0)View Category »Environmental Sensors

NTI Part # Description Qty
ENVIROMUX-STS Temperature Sensor
ENVIROMUX-SHS Humidity Sensor
ENVIROMUX-STHS Temperature/Humidity Combination Sensor
ENVIROMUX-STHS-99 Temperature/Wide Range Humidity Combination Sensor (up to 99% RH)
ENVIROMUX-SHS-PLT Precision Humidity Sensor
ENVIROMUX-STHS-PLT-120 Precision Temperature/Humidity Sensor, 20 to 120°F (-6 to 48°C)
ENVIROMUX-STHS-PLT-140 Precision Temperature/Humidity Sensor, -20 to 140°F (-28 to 60°C)
ENVIROMUX-STHS-PLT-180 Precision Temperature / Humidity Sensor, 30 to 180°F (-1 to 82°C)
ENVIROMUX-STHS-WLM Wall Mount Temperature/Humidity Sensor
ENVIROMUX-STHS-DCT Duct Mount Temperature/Humidity Sensor
ENVIROMUX-STSP-xx Pipe Temperature Sensor. To order, select Length of CAT5e Cable (x) Configure
ENVIROMUX-STS-O Outdoor Temperature Sensor
ENVIROMUX-SDS Smoke Detection Sensor
ENVIROMUX-AV Air Velocity Sensor - Requires ENVIROMUX-S5VDC
ENVIROMUX-S5VDC 5VDC Sensor Converter - Connects two linear DC sensors to ENVIROMUX-SEMS-16
ENVIROMUX-CMD Carbon Monoxide Detector
ENVIROMUX-LDSx-y Liquid Detection System. To order, select Configure to specify Length of Water Sensor Cable (x), and length of 2-Wire Cable (y) Configure

(0)View Category »Motion / Intrusion / Vibration Sensors Compatible with ENVIROMUX-SEMS-16

NTI Part # Description Qty
ENVIROMUX-M-DCS Door Contact Sensor
ENVIROMUX-VSS Vibration Sensor
ENVIROMUX-RKS Key Station
ENVIROMUX-LIS Light Intensity Sensor
ENVIROMUX-EBS Emergency / Panic Button
ENVIROMUX-GBS Glass Break Detection Sensor
ENVIROMUX-IMD Infrared Motion Sensor
ENVIROMUX-IMD-MW Mini Infrared Motion Sensor
ENVIROMUX-ACK Digital Keypad
ENVIROMUX-IMD-CM Ceiling Mount Infrared Motion Sensor
ENVIROMUX-EDR-SF Electric Strike Door Release (fail safe)
ENVIROMUX-EDR-SCR Electric Strike Door Release (fail secure)
ENVIROMUX-MB-IMD Mounting Bracket for Infrared Motion Sensor

(0)View Category »Alert & Communication Accessories Compatible with ENVIROMUX-SEMS-16

NTI Part # Description Qty
ENVIROMUX-BCN-R Alarm Beacon
ENVIROMUX-AVDS Automatic Voice Dialer System, Four Input Channels
ENVIROMUX-AVDS-LC Automatic Voice Dialer System, One Input Channel
ENVIROMUX-IPCAM IP Surveillance Cameras
ENVIROMUX-IPCAM-W IP Surveillance Wireless Camera
ENVIROMUX-IPCAM-N IP Surveillance Cameras
ENVIROMUX-IPCAM-WN IP Surveillance Cameras
ENVIROMUX-SRN-M Siren
ENVIROMUX-3G 3G Serial Modem, Powered
ENVIROMUX-GSMA Serial GSM Modem with Antenna
ENVIROMUX-3GU 3G Serial Modem, Powered

(0)View Category »Power Relays & Sensors Compatible with ENVIROMUX-SEMS-16

NTI Part # Description Qty
ENVIROMUX-ACVD-515 AC Voltage Detector with NEMA 5-15 plug (if using with ENVIROMUX-MINI use with ones purchased before 11/1/2007)
ENVIROMUX-ACVD-C14 AC Voltage Detector with IEC C14 socket (if using with ENVIROMUX-MINI use with ones purchased before 11/1/2007)
ENVIROMUX-S60VDC DC Voltage Detecter Converter
ENVIROMUX-ACLM-P12 AC Power Monitor with Relay 12A
ENVIROMUX-ACLM-P8 AC Power Monitor with Relay 8A
ENVIROMUX-ACLM-V AC Dual Voltage Monitor
ENVIROMUX-PWR-RLY-15A Remote Controlled Power Relay, 120VAC 15A
ENVIROMUX-PT1M-208-0800 3-Phase Power Transducer, for balanced loads, 1 Medium CT, 208VAC, 800A - Requires ENVIROMUX-S420MA
ENVIROMUX-PWR-RLY-20A Remote Controlled Power Relay, 120VAC 20A
ENVIROMUX-PT3M-208-0800 3-Phase Power Transducer, for unbalanced loads, 3 Medium CTs, 208VAC, 800A - Requires ENVIROMUX-S420MA
ENVIROMUX-PT3S-480-0100 3-Phase Power Transducer, for unbalanced loads, 3 Small CTs, 480VAC, 100A - Requires ENVIROMUX-S420MA

(0)Optional Extension Rail Kit

NTI Part # Qty
ENVIROMUX-RL-SEMS

(0)Sensor Extension Cables Connect dry contact sensors to the ENVIROMUX-SEMS-16

NTI Part # Length Qty
ENVIROMUX-2W-3 3 feet
ENVIROMUX-2W-6 6 feet
ENVIROMUX-2W-10 10 feet
ENVIROMUX-2W-25 25 feet
ENVIROMUX-2W-50 50 feet
ENVIROMUX-2W-100 100 feet

(0)4-20mA Sensor Converter Monitors 4-20mA Analog Sensors

NTI Part # Description Qty
ENVIROMUX-S420MA Power Converter